Chapter 8 Parameters ASDA-A2
8-136 Revision February, 2017
P3-xx Communication Parameters
P3-00
ADR Address Setting
Address: 0300H
0301H
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0x7F
Control
Mode
ALL
Unit
-
Range
0x01 ~ 0x7F
Data Size
16-bit
Format
Hexadecimal
Settings
The communication address setting is divided into Y, X (hexadecimal):
0 0 Y X
Range
0 ~ 7 0 ~ F
When using RS-232/RS-485 to communicate, one servo drive can only
set one address. The duplicate address setting will cause abnormal
communication.
This address represents the absolute address of the servo drive in
communication network. It is also applicable to RS-232, RS-485,
CANopen and DMCENT.
When the communication address setting of MODBUS is set to 0xFF,
the servo drive will automatically reply and receive data regardless of
the address. However, P3-00 cannot be set to 0xFF.
ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-137
P3-01 BRT Transmission Speed
Address: 0302H
0303H
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0x0203
Control
Mode
ALL
Unit
bps
Range
0x0000 ~ 0x0405
Data Size
16-bit
Format
Hexadecimal
Settings
The setting of transmission speed is divided into Z, Y, X (hexadecimal):
U Z Y X
Communication
Port
DMC CAN / DMC
RS-232/485
Range 0 / 3 0~4 0 0~5
Definition of X setting value
0: 4800
1: 9600
2: 19200
3: 38400
4: 57600
5: 115200
Definition of Z setting value
0: 125 Kbit/s
1: 250 Kbit/s
2: 500 Kbit/s
3: 750 Kbit/s
4: 1.0 Mbit/s
Definition of Z setting value
0: Use Delta’s controller, such as PLC and HMI
3: Use Delta’s motion card
NOTE
1If this parameter is set via CAN, only Z can be set and the others
remain.
2The communication speed of USB is 1.0 Mbit/s only and is
unchangeable.
Chapter 8 Parameters ASDA-A2
8-138 Revision February, 2017
P3-02 PTL Communication Protocol
Address: 0304H
0305H
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
6
Control
Mode
ALL
Unit
-
Range
0 ~ 0x8
Data Size
16-bit
Format
Hexadecimal
Settings
The definition of the setting value is as the followings:
0: 7, N, 2 (MODBUS, ASCII)
1: 7, E, 1 (MODBUS, ASCII)
2: 7, O,1 (MODBUS, ASCII)
3: 8, N, 2 (MODBUS, ASCII)
4: 8, E, 1 (MODBUS, ASCII)
5: 8, O, 1 (MODBUS, ASCII)
6: 8, N, 2 (MODBUS, RTU)
7: 8, E, 1 (MODBUS, RTU)
8: 8, O, 1 (MODBUS, RTU)
P3-03 FLT Communication Error Disposal
Address: 0306H
0307H
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0
Control
Mode
ALL
Unit
-
Range
0 ~ 0x1
Data Size
16-bit
Format
Hexadecimal
Settings
The definition of the setting value is as the following:
0: Warning and keeps running
1: Warning and stops deceleration (The deceleration time is set to
parameter P5-03.B)
ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-139
P3-04 CWD Communication Timeout
Address: 0308H
0309H
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0
Control
Mode
ALL
Unit
sec
Range
0 ~ 20
Data Size
16-bit
Format
DEC
Settings
If the setting value is not 0, enable communication timeout
immediately. If it is set to 0, disable the function.
P3-05 CMM Communication Mechanism
Address: 030AH
030BH
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0
Control
Mode
ALL
Unit
-
Range
0x00 ~ 0x01
Data Size
16-bit
Format
Hexadecimal
Settings
Communication port can select one or more than one communications.
Communication Interface
0: RS232
1: RS485
Chapter 8 Parameters ASDA-A2
8-140 Revision February, 2017
P3-06
SDI Control Switch of Digital Input (DI)
Address: 030CH
030DH
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0
Control
Mode
ALL
Unit
-
Range
0x0000 ~ 0x3FFF
Data Size
16-bit
Format
Hexadecimal
Settings
The source of DI controls the switch.
Each bit of this parameter decides one input source of DI signal:
Bit0 ~ Bit7 correspond to DI1 ~ DI8.
Bit8 ~ Bit13 correspond to extended DI EDI9 ~ EDI14;
The setting of bit is as the followings:
0: The input status is controlled by the external hardware.
1: The input status is controlled by P4-07.
For the functional planning of digital input, please refer to:
DI1 ~ DI8: P2-10 ~ P2-17
EDI9 ~ EDI14: P2-36 ~ P2-41
P3-07 CDT Communication Response Delay Time
Address: 030EH
030FH
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0
Control
Mode
ALL
Unit
1ms
Range
0 ~ 1000
Data Size
16-bit
Format
Decimal
Settings
Delay the time of communication response from servo drive to
controller
ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-141
P3-08
MNS Monitor Mode
Address: 0310H
0311H
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0000
Control
Mode
ALL
Unit
-
Range
Shown as below
Data Size
16-bit
Format
Hexadecimal
Settings
The setting of monitor mode is divided into L and H. (hexadecimal):
Item
L H
Function
Low-speed monitoring
time
Monitor Mode
Range 0 0 0 ~ F 0 ~ 3
The status of this axis or multi-axis can be monitored by USB. The
definition of setting value is as follows:
The definition of H setting value
3: USB is high-speed monitor. The sampling frequency is 16K and
can only monitor 2CH.
2: USB is high-speed monitor. The sampling frequency is 8K and
can monitor 4CH.
1: USB is low-speed monitor. The sampling time is set by L and
can monitor 4CH.
0: disable the monitor function
L: the sampling time of USB low-speed monitor. Its unit is ms.
It means the axial status will be set via USB every L ms. So the
controller can monitor the axial status. Each monitoring message
includes 4 CH data (16 bit x 4). If L is set to 0, this function is
disabled. L is enabled when H is set to 1.
Chapter 8 Parameters ASDA-A2
8-142 Revision February, 2017
P3-09 SYC CANopen / DMCNET Synchronize Setting
Address: 0312H
0313H
Operational
Interface
Panel / Software Communication
Related Section:
9.2
Default
0x5055 (for -B, -L, -M, -U type)
0x3511 (for -F type)
Control
Mode
CANopen / DMCNET
Unit
-
Range
Shown as below
Data Size
16-bit
Format
Hexadecimal
Settings
The synchronous setting of CANopen / DMCNET is divided into E, T, D
and M (hexadecimal):
Item E T D M
Function
Range of
Synchronous
error
Target Value Deadband
Adjusting
amount
Range 1 ~ 9 0 ~ 9 0 ~ F 1 ~ F
The slave of CANopen / DMCNET synchronizes with the master via
SYNC. See as the followings:
M: If the slave needs to synchronize with the master, correct the clock
is a must. This parameter sets the maximum correction value per
time. (Unit: usec)
D: Set the size of deadband (Unite: usec). If the deviation between the
SYNC reaching time and the target value does not exceed the
deadband, correction is no need.
T: SYNC arrival time. The standard value is 500usec but it might be
different from the target value. Thus, the buffer is necessary.
Target value400 + 10 x T.
For instance, if T=5, the target value will be 450.
E: If the deviation between SYNC reaching time and the target value is
smaller than the range, it means the synchronization is successful.
(Unit: 10 usec)
ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-143
P3-10 CANEN CANopen / DMCNET Protocol Setting
Address: 0314H
0315H
Operational
Interface
Panel / Software Communication
Related Section:
Section 9.2
Default
0x0000
Control
Mode
CANopen / DMCNET
Unit
-
Range
Shown as below
Data Size
16-bit
Format
Hexadecimal
Settings
CANopen / DMCNET synchronization setting is divided into X, Y, Z, U
(hexadecimal):
Item U Z Y X
Function
If PDO alarm
will be cleared
automatically
Reserved
If motor will
servo off
when CAN
Bus /
DMCNET
error occurs
Reserved
Range 0 ~ 1 0 ~ F 0 ~ 1 0 ~ 1
Definition:
X: Reserved
Y: 0: The motor keeps running when communication error occurs;
1: The motor servo Off when communication error occurs.
Z: Reserved
U: 0: If PDO error occurs, it must be cleared by Alarm Rest
1: If PDO error occurs, it will be cleared automatically.
Note:
For A2-M, X bit is invalid.
For A2-F, it is suggested to set X to 1.
Chapter 8 Parameters ASDA-A2
8-144 Revision February, 2017
P3-11 CANOP CANopen / DMCNET Selection
Address: 0316H
0317H
Operational
Interface
Panel / Software Communication
Related Section:
Section 9.2
Default
0x0000
Control
Mode
CANopen / DMCNET
Unit
-
Range
Shown as below
Data Size
16-bit
Format
Hexadecimal
Settings
Synchronous / DMCNET setting of CANopen is divided into X, Y, Z and
U (hexadecimal):
Item U Z Y X
Function Undefined Undefined Undefined
Whether the
parameter is saved
into EEPROM
Range -0 ~ 1 0 ~ F 0 ~ F 0 ~ 1
The definition is as follows:
X = 1: When writing parameters via PDO, parameters will be saved in
EEPROM.
X = 0: When writing parameters via PDO, parameters will not be saved
in EEPROM.
Y, Z, U : Undefined
If X is set to 1 and write parameters by PDO continuously, it will
shorten the lifetime of EEPROM.
P3-12 QSTPO CANopen / DMCNET Support Setting
Address: 0318H
0319H
Operational
Interface
Panel / Software Communication
Related Section:
Section 9.2
Default
0x0000
Control
Mode
CANopen / DMCNET
Unit
-
Range
0x0000 ~ 0x0111
Data Size
16-bit
Format
Hexadecimal
NOTE
ASDA-A2 Chapter 8 Parameters
Revision February, 2017 8-145
Settings
CANopen / DMCNET synchronization setting is divided into X, Y, Z, U
(hexadecimal):
Item U Z Y X
Function None
CANopen /
DMCNET
value will be
loaded in
If the motor will enter
Quick Stop mode
when in auto
protection.
If OD-6040
supports
Quick Stop
Range None 0~1 0 ~ 1 0 ~ 1
Aiming to CANopen Quick Stop mode, we have X and Y setting
(Hexadecimal.) which is showed as below. It is only suitable in CAN
mode: oxb mode selection (P1-01 = b).
X: Trigger Servo ON sequence and Quick Stop support setting
X = 0: Servo On the servo drive by turning On OD-6040 Bit 3 (Enable
Operation). OD-6040 Bit 2 enters Quick Stop mode is not
supported.
X = 1: The servo drive can be Servo ON only when OD-6040 Bit 0, Bit
1, Bit 3 are ON. And will enter Quick Stop mode via OD-6040 Bit
2 (Quick Stop)
Y: When warning alarms (positive / negative limit, communication error,
under voltage, abnormal fan) occur, it can determine if Quick Stop
mode can be triggered.
Y = 0: When warning alarms occur, if motor decelerates to stop
because of auto protection function, it will not enter Quick Stop
mode. Users only need to troubleshoot the alarm and clear the
alarm message from the servo drive, the servo drive status will
resume.
Y = 1: When warning alarms occur, if motor decelerates to stop
because of auto protection function, OD-6040 will enter Quick
Stop mode. Users have to issue Fault Reset to continue other
commands and clear the alarm message from the servo drive.
The following table shows P parameters and its corresponding
CANopen OD or DMCNET parameter. The setting of Z (Hexadecimal.)
can determine if it should be modified. This function is applicable in
CAN mode: 0xB or 0xC (P1-01 = b or c) or DMC mode: 0xB (P1-01 =
b).
Z: Determine if the value of OBJECT will overlap parameters from P
groups.
Z = 0: When re-servo on the servo drive or reset the communiation, P
parameters that mentioned in the following table will load in the
default value in CANopen /DMCNET mode.
Z = 1: When re-servo on the servo drive or reset the communiation, P
parameters that mentioned in the following table will keep the value
that before power off.
CANopen mode:
Related variables
during initialization
P3-12.Z = 0 P3-12.Z = 1 Note
P1-32
0x0010 EEPROM
P2-35
3840000
EEPROM
Chapter 8 Parameters ASDA-A2
8-146 Revision February, 2017
P1-47 10 EEPROM
P1-49 0 EEPROM
P1-38 100 EEPROM
Home offset
0 EEPROM Used in HM
mode
P1-44
1
EEPROM
P1-45
1
EEPROM
DMCNET mode:
Related variables
during initialization
P3-12.Z = 0 P3-12.Z = 1 Note
P1-32
0x0010 EEPROM
P2-35
3840000
EEPROM
P1-47
100 EEPROM
P1-49
0 EEPROM
P1-38
100 EEPROM
Home offset
0 Undefined Used in HM
mode
Acc
200 Undefined Used in PV, PP
mode
Dec
200 Undefined Used in PV, PP
mode
P1-44
1 EEPROM
P1-45
1 EEPROM
Methods that save parameters in EEPROM (even when the power is
off):
SDO: When setting parmeters, parameters will be stored in EEPROM.
PDO: Please refer to the setting of P3-11.X
X = 1: When setting parameters via PDO, parameters will be stored in
EEPROM.
X = 0: When setting parameters via PDO, parameters will not be stored
in EEPROM.
Note: In CANopen mode, when using the funciton of OD 1010 Store
Parameter and P3-12.Z = 0, the default value will be different from the value
that showed above. Please refer to CANopen Standard for further information.