| Name | Description | ALM | WRN | SRV ON | Clear Way | 
|---|---|---|---|---|---|
| AL.002 Over Voltage | The voltage of the main circuit is higher than the standard voltage. | ⊗ | NO | DI.ARST | 
| Causes | Checking Method | Actions | 
|---|---|---|
| The input voltage of the main circuit is higher than the rated allowable voltage | Use the voltmeter to see if the input voltage of the main circuit is within the rated allowable voltage value (please refer to Chapter 12.1) | Apply to the correct power supply or serial voltage regulator | 
| Wrong power input (incorrect power system) | Use the voltmeter to see if the power system matches the specification | Apply to the correct power supply or serial adaptor | 
| The hardware of the servo drive is damaged | Use the voltmeter to see if the input voltage of the main circuit is within the rated allowable voltage value but still shows the error | Send the drive back to the distributors or contact with Delta | 