| Name | Description | ALM | WRN | SRV ON | Clear Way | 
|---|---|---|---|---|---|
| AL.005 Regeneration Error | Regeneration control is in error | ⊗ | NO | DI.ARST | 
| Causes | Checking Method | Actions | 
|---|---|---|
| The regenerative resistor is unconnected or too low | Check the connection of regenerative resistor | Reconnect the regenerative resistor or calculate the value of the regenerative resistor | 
| Parameter P1-53 is not set to zero when the regenerative resistor is not in use | Check if parameter P1-53 of regenerative resister is set to zero | Set parameter P1-53 of regenerative resistor to zero when it is not applying | 
| Wrong parameter setting | Check the setting value of parameter P1-52 and P1-53 | Correctly reset the setting | 
(The above information is referenced from Delta Electronics IMSBU)