<= See All alarms of Delta servo
Name | Description | ALM | WRN | SRV ON | Clear Way |
---|---|---|---|---|---|
AL.085 Regeneration setting error |
Regeneration control error | ⊗ | No | DI.ARST ↑ |
Causes | Checking Method | Actions |
---|---|---|
Choose wrong regenerative resistor or does not connect to external regenerative resistor. |
Check the connection of regenerative resistor. | Calculate the value of the regenerative resistor again and correctly set the values of P1-52 and P1-53. If the issue persists, please send the drive back to the distributors or contact Delta. |
Parameter P1-53 is not set to zero when the regenerative resistor is not in use. | Check if parameter P1-53 of regenerative resister is set to zero. | Set parameter P1-53 of regenerative resistor to zero when it is not applying. |
Wrong parameter setting | Check the setting value of parameters P1-52 and P1-53. | Correctly reset the values of P1-52 and P1-53. |
(The above information is referenced from Delta Electronics IMSBU)
See ALL Alarms <= ↓ The following content is contributed by users ↓
Other reasons | Checking Method | Actions |
---|---|---|
— Sharing is a virtue. Please add the inadequacies of this article to benefit the public —